What counts as hot work
Hot work is any activity that produces flame, sparks, high temperature or heated metal in a place where combustible materials, vapours or dusts may be present. Typical examples are electric and gas welding, cutting with a torch or angle grinder, hard soldering, use of a heat gun and work with hot asphalt.
Article 208 of the Polish Labour Code requires employers working in the same place to coordinate safety, and the general occupational health and safety and fire protection regulations require special measures for work with increased hazard. In practice a plant captures this in an internal procedure: a list of jobs that need a written permit, the roles of the people involved and requirements for contractors.
Scale in an industrial plant
In an analysis of 106 permits over 9 weeks in a continuous-process production plant, 43 concerned work with fire, which is about 40% of all permits. Hot work is therefore not an exception but a constant part of the work of maintenance teams and outside contractors.
Step 1: work request and fire hazard assessment
The process starts with a request: who will do what, where and when. The request must name the exact work location, not just the building, because the assessment depends on what lies within the spark radius and on the levels below. A warehouse hall with racking and a production hall with a line are two different risk profiles.
A fire hazard assessment answers four questions. Are there combustible materials, liquids, gases or dusts at the work location or nearby? Can sparks and hot metal get through openings, gaps, cable ducts or penetrations into rooms next door or below? Are there combustible materials on the other side of the partition being worked on? Can the job be done outside the hazard zone, for example in a workshop?
If the job can be done without fire, for example with a mechanical joint instead of welding, the plant should choose that method. A hot work permit is the last resort, not the first.
Share of hot work in permits (9 weeks)
Step 2: permit, site preparation and measurements
A hot work permit is a document that brings together the location, scope, time, people, safeguards and signatures. It is issued by a person authorised by the plant and approved by the person responsible for the area. The document has a defined time window: when it expires, the work ends or the permit is extended by a conscious decision.
Before work starts the site must be prepared, not only described on paper:
- remove or shield combustible materials in the work zone, and cover those that cannot be removed with non-combustible blankets
- seal openings, gaps and penetrations through which sparks could travel
- in explosion-risk areas, measure gas concentration before the job and repeat the measurement at set intervals
- prepare extinguishing equipment suited to the materials in the zone and check that it is available
- switch off or isolate installations that could feed a fire or explosion, if the procedure requires it
Sequence matters
Measurement after securing the site, signature after measurement, start of work after signature: the sequence is part of safety. On paper nobody enforces it, so in practice a signature sometimes comes before the measurement. In an electronic system the order of steps can be enforced through the permit template configuration.
Step 3: carrying out the work and supervision
Three roles are present during the job. The permit issuer is responsible for the correctness of the document. The supervising person, that is the works manager on the contractor or plant side, ensures that the work follows the permit conditions. The fire watch, also called the fire guard, observes the site throughout the job with an extinguisher within arm's reach and has one task: to react to ignition.
The fire watch does not weld and does not hand over tools. If one person performs both roles, the watch is only nominal. The plant should require in its procedure that a separate person is appointed and that this person has been trained in using extinguishing equipment.
When conditions change, for example the contractor has to uncover a hidden combustible material or the wind shifts during outdoor work, the permit should be suspended. Work resumes once the irregularity is removed, and the whole cycle should be recorded in the history.
Step 4: fire watch after the job and closing the permit
The most dangerous moment in hot work often begins after the work is finished. Smouldering residue, hot metal or a spark in a gap can develop into a fire only after many minutes. That is why the site needs a fire watch after the job: observation, visual inspection and, where possible, temperature checks.
The plant sets the length of the post-work watch in its procedure on the basis of a risk assessment. In InnerWeb, two post-work observation stages are implemented for hot work: one hour and four hours, with a closing lock until at least three hours have passed. This is a product rule that the plant configures to its own procedure, not a legal requirement. The system records the course of the observation but does not perform it: that is done by the fire guard on the contractor side.
Closing the permit
The permit is closed by the responsible person after inspecting the site and confirming that the watch time has elapsed. Closing without this confirmation is the most common gap in paper procedures, because the sheet comes back to the office with a signature, but nobody knows whether the watch actually took place.
Outside contractors and audit evidence
The greatest organisational risk appears when hot work is done by outside contractors. At one chemical plant about 20 outside companies work in maintenance, often admitted to hot work, work at height and work in tanks. Permits in binders do not give a current picture of open jobs, and training at the gate delays the start.
The solution is a single path: training before arrival, a permit with an enforced order of steps and control in the field. The system supports meeting the coordination requirement because it shows who is working where and on which permit, and it provides audit evidence: who issued it, who approved it, when the work started and ended and when the fire watch finished.
Checklist
Video
Frequently asked questions
Does every welding job need a permit?
It depends on the plant procedure. Usually a permit is required for every welding job outside a permanent, designated workshop station approved for such work. The plant should describe the rule and its exceptions in the procedure.
Who can issue a hot work permit?
A person named in the plant procedure, usually with the relevant authorisation and training. It is approved by the person responsible for the area where the work takes place.
Can the fire watch weld at the same time?
No. The watch is a task separate from the work. One person cannot run an arc and observe ignition at the same time.
Does a digital permit replace the procedure?
No. The medium changes, the procedure stays. The system mirrors the current procedure, roles and order of steps and supports compliance with it.
Sources
See the hot work permit in practice
Book a short demo on your own plant data. We will show how to mirror your hot work procedure without changing your instructions.